B70A General features
Sensitive element with friction membrane.
Adjustable differential.
Female connection G 1/4.
Cover in shockproof thermoplastic material.
Metallic parts are in steel.
Earth clamp.
Output connections with two cable glands.
Maximum temperature of the controlled fluid: 90°C.
Pressure switch body admissible temperature: -15 ÷ 60°C.
Storage and transport temperature: -35 ÷ 60°C.
Unit weight: 0.39 Kg.
Electric features
Rated insulation voltage Ui 415V~
Continuous duty rated current Ith 25A


CODE : B70A
RANGE : 0.5 ÷ 7 bar
DIFFERENTIAL
START OF SCALE
: 0.8 bar
DIFFERENTIAL
FULL SCALE : 1.8 bar
MAXIMUM
DIFFERENTIAL : 3.5 bar
PROTECTION
DEGREE : IP40


Click below to download the product-related documents